FEBEX Module Control

The FEBEX Control page allows all settings in the module firmware to be set and monitored.

The top row of parameters define the FEBEX board and ADC channel (if applicable) to be accessed. You can select that write commands apply to all boards and/or all links.
Additionally write actions can apply to a selection of ADC channels or all ADC channels.
Not all actions apply on a per channel basis in which case the channel parameter is ignored.


Global Options:              Channel:               currently ignored
                             Trace Length:          not channel dependent

Trigger Options:             channel dependent
CFD Settings                 channel dependent

Moving Window Deconvolution:     M:      length of step signal from exponential tail            channel dependent
                                 L:      length of moving average                               channel dependent
                                 Torr:   preamp time in clock cycles                            channel dependent
                                 B:      number of clock cycles to blank the baseline           channel dependent
                                         after a trigger
                                 O:      Options  (see documentation)                           channel dependent
                                 CTD:    CFD Trigger Delay   -  number of clock cycles          channel dependent
                                         after trigger to sample the energy

Trigger Matrix:                  Window:  aggregation of triggers over Window clock cycles      channel independent
                                 Trigger Matrix Setup     starts independent page
                                 
Others:                          Show Registers           starts independent page 

The FEBEX board settings made via this page can the saved and restored using "Page G: FEBEX Settings Save/Restore"

V Pucknell; STFC; Daresbury Lab   updated 10 MArch 2022